Against the backdrop of surging computing demand driven by generative AI and large model training, the power density of high-performance servers continues to rise, making equipment thermal management a critical bottleneck that limits the stable operation of data centers. Traditional air-cooling technologies face limitations in cooling efficiency and energy consumption when confronted with single-cabinet power densities of 20 kW or higher, prompting liquid cooling to shift from an alternative to a mainstream solution. In the engineering implementation of liquid cooling systems, the real challenge lies not merely in achieving adequate cooling, but in ensuring that the coolant is delivered reliably, precisely, and safely to every server—a goal that heavily depends on the selection, configuration, and performance of valves within the liquid cooling system.
If the liquid cooling system is likened to the human circulatory system, with the cold-distribution unit serving as the “central heart,” then the various valves distributed throughout the piping network assume the role of “vascular valves,” responsible for flow regulation, pressure stabilization, and safety protection. With respect to the CDU and the liquid-cooling piping system, valve applications can be examined from the following perspectives:
1. On/Off & Isolation:
Basic guarantee for system operation and maintenance
In liquid cooling systems, ball valves and solenoid valves perform the fundamental functions of shut-off and isolation. Ball valves are typically made of 304 stainless steel with a full-bore design and are installed at cabinet outlets, system low points for drainage, and similar locations to enable manual, rapid branch circuit isolation, supporting maintenance without shutting down the system. Solenoid valves handle automatic, rapid on/off operations with a response time requirement of less than 50 milliseconds, used for branch circuit switching and emergency shutdown scenarios. Given data centers’ “zero tolerance” for coolant leaks, these valves must meet helium mass spectrometry leak-test standards (leak rate <1×10⁻⁹ Pa·m³/s), far exceeding requirements for typical industrial applications.
2. Regulation & Balance:
The Core of Precise Cooling Capacity Distribution
This is the most technologically advanced stage of valve operation and has the most direct impact on cooling efficiency. The electric control valve installed at the CDU outlet serves as the core actuator for intelligent liquid cooling; it receives control signals from the DCIM system (e.g., 4–20 mA or 0–10 V) and dynamically adjusts the coolant flow rate in real time based on each cabinet’s load (with a per-cabinet flow range of approximately 10–50 L/min). Valve position control accuracy must reach ±1% of full scale. Meanwhile, static balancing valves compensate for resistance imbalances among parallel circuit branches—since cabinets closer to the pump experience higher pressure and greater flow, while those at the far end suffer insufficient flow. By calibrating preset openings, balancing valves achieve hydraulic balance across the entire system, directly influencing PUE performance. In AI-driven high-density computing scenarios, GPU rack loads fluctuate dramatically, placing demands on control valve response speed and precision that far exceed those of traditional data centers.
3. Safety Protection:
The system’s last line of defense
Check valves, safety valves, and quick-connect valves address three distinct risk scenarios. The check valve is installed at the pump outlet; its spring-assisted design ensures rapid closure when the pump stops, preventing coolant backflow and mitigating water hammer. The safety valve serves as the system’s final safeguard, typically set to 1.1–1.2 times the maximum operating pressure; it provides forced relief in case of over pressure and must comply with international standards such as ASME or PED. Meanwhile, the quick-connect valve resolves a major operational challenge associated with high-density environments by enabling “hot-swapping” of servers without draining the coolant or shutting down the system, reducing the time required to address a single rack failure from hours to minutes.
4. Media Compatibility and Cleanliness:
The Hidden Threshold of High Reliability
Coolant systems use a variety of media (deionized water, ethylene glycol solutions, fluorinated liquids, etc.), placing stringent demands on valve materials. Because deionized water has an extremely low ion concentration, brass valve bodies are strictly prohibited (zinc leaching can contaminate the coolant and clog the cold plate’s microchannels); 304/316L stainless steel valve bodies with EPDM or FKM seals must be used. Fluorinated liquids are more corrosive to sealing materials, requiring perfluoroelastomer (FFKM) and verification through third-party compatibility immersion testing. Furthermore, the internal cleanliness of the valves must meet NAS 1638 Class 6 or higher to ensure no particulates enter the server cold plate.
As the penetration rate of liquid cooling continues to rise, valves—key components characterized by their small size, stringent requirements, and zero tolerance for failure—are moving from a supporting role to center stage, becoming one of the core battlegrounds in the competition for reliability and energy efficiency in liquid-cooling systems.